Herunterladen Inhalt Inhalt Diese Seite drucken

Installation Of The Outdoor Unit - Toshiba MMY-MUP0801HT8P-E Installationsanleitung

Vorschau ausblenden Andere Handbücher für MMY-MUP0801HT8P-E:
Inhaltsverzeichnis

Werbung

Verfügbare Sprachen
  • DE

Verfügbare Sprachen

  • DEUTSCH, seite 14
6

Installation of the outdoor unit

WARNING
• Be sure to install the outdoor unit in a place able to bear its weight.
If strength is insufficient, the unit may fall down resulting in human injury.
• Perform specified installation work to protect against strong wind and earthquakes.
If the outdoor unit is imperfectly installed, an accident by falling or dropping may be caused.
CAUTION
• Drain water is discharged from the outdoor unit. (Especially while heating)
Install the outdoor unit in a place with good drainage.
• For installation, be careful of the strength and level of the foundation so that abnormal sounds (vibration or
noise) are not generated.
REQUIREMENT
Installation in a snowfall area
1. Install the outdoor unit on a higher foundation than the snowfall or set up a stand to install the unit so that
snowfall will not affect the unit.
• Set up a stand higher than the snowfall.
• Apply an angled structure to the stand so that drainage will not be prevented. (Avoid using a stand with a flat
surface.)
2. Mount a snowfall-hood onto the air intake and the air discharge.
• Leave enough space for the snowfall-hood so that it will not be an obstacle for the air intake and the air
discharge.
1. To install multiple outdoor units, arrange them with 20 mm or more spaces in between.
Fix each outdoor unit with M12 anchor bolts at 4 positions. 20 mm projection is appropriate for an anchor bolt.
20 mm or more 20 mm or more
117-EN
IM_1141001201-2_Book.indd 59
IM_1141001201-2_Book.indd 59
Snowfall-hood for air
discharge
(locally procured)
Snowfall-hood for air
discharge
(3 faces)
(locally procured)
Stand
(locally procured)
M12 anchor bolt
4 positions/unit
– 59 –
• Anchor bolt positions are as shown below:
766
244 or more
700
310 or more
2. When drawing out the refrigerant pipe from the
underside, set the height of the stand to 500 mm or
more.
4. Mount the vibration-proof rubber (including vibration-proof blocks) so that it fits under the whole clamping leg.
Correct
Install the vibration-proof
Anchor bolt
rubber so that the bent
part of the fixing leg is
Vibration-proof rubber
grounded.
Incorrect
The bent part of
the fixing leg is not
grounded.
(Unit : mm)
1076
239 or more
920
350 or more
1076
234 or more
920
390 or more
3. Do not use 4 stands on the corner to support the
outdoor unit.
Incorrect
Correct
Correct
Incorrect
Incorrect
5/2/2564 BE 16:27
5/2/2564 BE 16:27
118-EN

Quicklinks ausblenden:

Werbung

Inhaltsverzeichnis
loading

Inhaltsverzeichnis