TMD 834
Field
Parameter
V9H4

Bus address

0..125 , default value 126
Please note, if there are two devices with the same address no communication may
be established.
Field
Parameter
V2H0
Lower sensor limit
(read only)
V2H1
Upper sensor limit
(read only)
V2H2
Cold junction reference
No RJ - Internal - External
V2H3
External RJ value
V9H2
Product code
(read only)
V9H3
Software version
(read only)
V9H8
Fault codes
V9H9
Matrix password
VAH0
Tag number
Significance
Instrument address in the bus structure, selectable only by
software.
Significance
Value in engineering unit of minimum sensor temperature. E.g.
-200 for Pt 100. See technical data section for each sensor limit.
Value in engineering unit of maximum sensor temperature. E.g.
850 for Pt 100. See technical data section for each sensor limit.
For Tc inputs, compensation must be provided for ambient
temperature existing at the cold junction point. This is normally
provided by a precision sensor installed internally to the
TMD 834 transmitter. However the user may choose to set this
temperature compensation as an external parameter. See also
next field V2H3.
A value in engineering units must be entered here if in previous
field V2H2 is selected "external". Value may range from
-40 to 85 °C.
Contains information about product code of transmitter.
Contains information related to the instrument software version.
see chapter 5.2
Entering code 333 in this location, matrix will be unlocked.
Entering a three code digit number ≠ 333 the matrix is locked
(except V9H9). The measuring point is then protected against
accidental or unauthorised entries.
An 32 characters alpha-numerical string is available to enter
measuring point designation.
Chapter 4 Operation
Bus address
Other
43