Herunterladen Inhalt Inhalt Diese Seite drucken

Cable Entries; Cable Specification; Electrical Connection; Terminal Assignment And Connection Data: Power Supply - Endress+Hauser Proline Promass 40 Bedienungs- Und Sicherheitshinweise

Vorschau ausblenden Andere Handbücher für Proline Promass 40:
Inhaltsverzeichnis

Werbung

Verfügbare Sprachen

Verfügbare Sprachen

Proline Promass 40

Cable entries

Cable specification

Electrical connection

Terminal assignment and
connection data:
Power supply
Endress+Hauser
• For the connection compartment (Ex d version); power supply cable, circuit cable:
Choice of cable gland M20 × 1.5 or thread for cable entries ½" NPT or G ½".
Ensure that the Ex d cable glands/entries are secured against self-locking and the associated seals are
arranged directly on the housing.
• For connection compartment (Ex e version);
power supply cable, circuit cable: Choice of cable gland M20 × 1.5 or thread for cable
entries ½" NPT or G ½". The cables must be installed such that they are fixed in place. Adequate strain relief
must be ensured.
#
Warning!
When using cable glands M20 × 1.5:
• Only approved cable glands may be used (see Page 16 "Installation instructions").
• The cable glands must be very leak-tight.
You can find information about the cable specification in the associated Operating Instructions.
Connection compartment
Transmitter housing (terminal assignment, connection data → Page 21 ff.)
4...20 mA HART
27
+
26
25
+
24
e
23
+
22
21
+
20
d
N (L–)
2
L1 (L+)
1
Fig. 5:
Electrical connections
Power supply cable (terminal assignment, connection data → Page 21 )
a
Signal cable (terminal assignment, connection data → Page 22 )
b
c
Ground terminal for signal cable shield
d
Ground terminal for protective ground
e
Service adapter for connecting the service interface FXA193 (Fieldcheck, FieldCare)
All transmitters
Designation
Functional values
Intrinsically safe circuit
U
m
ATEX II2GD; IECEx Zone 1, Zone 21
b
c
a
1 L (+)
2 N (–)
Supply voltage
AC: U = 85 to 260 V;
AC: U = 20 to 55 V
DC: U = 16 to 62 V
Power consumption: 15 VA / 15 W
no
260 V AC
0
A0005611
*
Protective earth
Caution!
Observe the grounding plans
of the system!
21

Werbung

Inhaltsverzeichnis
loading