UNIT INSTALLATION

6 UNIT INSTALLATION
!
C A U T I O N
Transport the products as close to the installation location as possible
before unpacking.
Do not put any material on the products.
!
D A N G E R
Install
the
unit
with
sufficient
operation and maintenance as shown in the next figures.
Install the unit where good ventilation is available
Do not install the unit where there is a high level of oil mist, salty air
or sulphurous atmosphere.
Install the unit as far as practical (being at least 3 meters) from
electromagnetic wave radiator (such as medical equipment).
For cleaning, use noninflammable and nontoxic cleaning liquid. Use
of inflammable agent should cause explosion or fire.
Work with sufficient ventilation, for working in an enclosed space
should cause oxygen deficiency. Toxic gas should be produced when
cleaning agent is heated to high temperature by, e.g., being exposed
to fire.

6.1 INSTALLATION SPACE

(Unit: mm)
Around sides are open
500
7
PMML0342B rev.1 - 03/2016
All manuals and user guides at all-guides.com
clearance
around
it
for
Single installation
0<L≤1/2H→A≥350
1/2H<L≤H→A≥450
H=1380
Around sides are closed
500
Around sides are open with obstacles above
Install the unit in a location where noise emitted by the unit does not
disturb neighbours.
Cleaning liquid shall be collected after cleaning.
Pay attention not to clamp cables when attaching the service cover to
avoid electric shock or fire.
!
C A U T I O N
When installing more than one units together, keep clearance
between the units of more than 500 mm, and avoid obstacles that
should hamper air intake.
Install the unit in the shade or not exposed to direct sunshine or direct
radiation from high temperature heat source.
Do not install the unit in a space where a seasonal wind directly blows
to the Outdoor fan.
Make sure that the foundation is flat, level and sufficiently strong.
This unit has aluminium fins with sharp edges. Pay attention to the
fins to avoid injury. Install the unit in a restricted area not accessible
by the general public
Around sides are open with obstacles above
0<L≤1/2H→A≥600
1/2H<L≤H→A≥1200
H=1380
H=1380
0<L≤1/2H→A≥600
1/2H<L≤H→A≥1200
H=1380