Herunterladen Inhalt Inhalt Diese Seite drucken

Unit Installation; Initial Check - Hitachi RCIM-1.0FSN Installationsanleitung

Inhaltsverzeichnis

Werbung

Verfügbare Sprachen
  • DE

Verfügbare Sprachen

  • DEUTSCH, seite 29
2
UNITS INSTALLATION
2
CAUTION:
Do not install the indoor units in a flammable
-
environment to avoid a fire or an explosion.
Check to ensure that the ceiling slab is strong
-
enough. If not strong enough, the indoor unit may fall
down on you.
Do not install the indoor units, outdoor unit, remote
-
control switch and cable within approximately 3
meters of strong electromagnetic wave radiators
such as medical equipment.

2.1. UNIT INSTALLATION

2.1.1.
FACTORY-SUPPLIED ACCESSORIES
Accessory
Checking Scale
(Cut out from
Carton Board)
Flat Washer with
insulation (M10)
Washer (M10)
Drain Hose
Wire Clamp
Insulation
(Big Size)
Insulation
(Small Size)
Insulation (5t)
Band
Qty.
Purpose
1
For Unit Installation
4
4
1
For Drain Hose
Connection
1
1
For Refrigerant
Piping
Connection
1
For Drain Hose
1
Insulation
For Fixing
6
Refrigerant
Piping Insulation
Do not install the indoor units in a machinery shop or
-
kitchen where vapor from oil or mist flows to the
indoor units. The oil will deposit on the heat
exchanger, thereby reducing the indoor unit
performance, and may deform. In the worst case, the
oil damages the plastic parts of the indoor unit.
To avoid any corrosive action to the heat
-
exchangers, do not install the indoor units in an acid
or alkaline environment.
When lifting or moving the indoor unit, use
-
appropriate slings to avoid damage and be careful
not to damage the insulation material on units
surface.
2.1.2.

INITIAL CHECK

Install the indoor unit with a proper clearance around it
-
paying careful attention of installation direction for the
piping, wiring and maintenance working space, as shown
below.
Provide a service access door near the unit piping
-
connection area on the ceiling.
500 mm Min.
Piping Connection
Side
100 mm Min.
1000 mm Min.
Service Space
Check space between ceiling and false ceiling is enough
-
as indicated below.
Check the ceiling surface is flat for the air panel
-
installation work.
Check down slope Pitch of Drain Piping is following the
-
specifications indicated in Drain Piping Chapter.
100 mm Min.
100 mm Min.
Clearance:
10-20mm
Unit High
In False Ceiling

Werbung

Inhaltsverzeichnis
loading

Diese Anleitung auch für:

Rcim-1.5fsnRcim-2.0fsn

Inhaltsverzeichnis