Installation and connection (continued)
4.5

Shielding and cable routing

Defined ground!
The transducer and the control cabinet must be
at the same ground potential.
Shielding
To ensure electromagnetic compatibility (EMC), observe
the following:
Connect transducer and controller using a shielded
cable.
Shielding: Braided copper shield with minimum 85%.
Connector version: Shield is internally connected to
connector housing.
Cable version: On the transducer side, the cable
shielding is connected to the housing. Ground the
cable shielding on the controller side (connect with the
protective earth conductor).
Magnetic fields
The linear encoder is a magnetostrictive system. It is
important to maintain adequate distance between the
transducer/holding cylinder and strong, external magnetic
fields.
Cable routing
Do not route the cable between the transducer, controller,
and power supply near high voltage cables (inductive stray
noise is possible).
The cable must be routed tension-free.
Bending radius for fixed cable
The bending radius for a fixed cable must be at least five
times the cable diameter.
Cable length
BTL7-A/G
Max. 30 m
1)
Prerequisite: Construction, shielding and routing preclude the effect of any
external noise fields.
Tab. 4-4:
Cable lengths BTL7