BES M12EH1-L01C40B-S04G-L04 / BES M18EH1-L01C80B-S04G-L04
Inductive sensors
5
Installation and connection
5.1
Preparing for installation
Quasi-flush mountable sensors require a space behind the
active surface which is free of conductive installation
materials. The minimum permissible distance between the
sensor surface and installation material is designated
dimension X (see Fig. 5-1). The dimension X is 1 mm.
The deviation in the effective operating distance associated
with the installation is maximum 10%.
d
≥4d
X
Active surface
Fig. 5-1:
Quasi-flush mounting with dimension X
5.2
Installation
For dimensions, see Fig. 4-1 on page 8.
► Install the sensor so that it is protected from
electromagnetic fields and mechanical damage.
www.balluff.com
≥4d
≥3Sn
5.3
Electrical Connection
1
2
4
3
Fig. 5-2:
Plug layout (top view of M12 plug on sensor)
Pin Signal
1
L+ (Operating voltage +, SIO 10...30 V,
IO-Link 18...30 V)
2
I/Q (digital input / digital output)
3
L− (Operating voltage −)
4
C/Q (IO-Link communication / digital output in SIO
mode / digital input)
Tab. 5-1:
Pin assignment
5.4
Shielding and cable routing
Cable length
For IO-Link operation, the maximum cable length is 20 m.