Calibration procedure (continued)
6.3

Calibration procedure overview

6.3.1

Adjusting

The detailed procedure for adjusting is
described on page 15 ff.
The factory set null point and end point is replaced by a
new start point and end point and the associated output
values can be adjusted. The start and end values can be
adjusted as you like up to the limits. Both outputs can be
set separately.
Steps
► Move magnet to the new start position.
► Read new start point by pressing the buttons.
► Set the new start value by pressing the buttons.
New start value
New null point
Fig. 6-2:
Adjust a new start value
14
english
► Move magnet to the new end position.
► Read new end point by pressing the buttons.
► Set the new end value by pressing the buttons.
New end value
Fig. 6-3:
Adjust a new end value
6.3.2

Reset

Restoring the transducer to its factory settings.
Before
The detailed procedure for the reset is
described on page 19.
After
Before
After
New end point