Earthing Protection
This section outlines the information for installation
of Wallbox Pulsar Plus in the UK region.
Part Numbers Affected: PLP1-X-X-2-F-XXX-A
In the UK region, the PME system with an incoming earthing point is
widely used by residential and business electricity consumers. The RCCB
does not provide protection against open circuit PME faults, so touch
voltage hazards could occur without triggering a disconnection of the
mains electricity supply to the building.
To follow and be compliant with
the regulations specified by IET
in clause 722.411.4.1(iv), Wallbox
Pulsar Plus uses a technology that
enables you to directly connect your
charger to a PME supply.
The Wallbox Pulsar Plus UK
charger now includes a safety
monitoring system to detect
potential earth-neutral faults. If
faults are detected in the circuit, the
charge cycle ends thus isolating the
vehicle from the power supply.
This removes the risk of touching
the vehicle and a potential shock if
earth-neutral fault is present.

Wiring Diagram

L1 L2 L3 N PE
L
PE
N
Note: Do not remove the cable connecting
the L3 and PE terminals.
29