w-MEXT
ELEVATED FLOOR PERFORATION FOR UNDER MACHINES
INFORMATION
By respecting the measures shown, a minimum distance of 5 cm (C)
is guaranteed from the wall behind the machine
Base support frame
Size
F1
520
A
mm
420
B
mm
2.2.3

MACHINE WALL INSTALLATION BRACKET

The bracket is supplied as assembly kit including the bolts for securing it to the machine.
This is a safety device that must be installed with the unit and secured to a structural
section of the installation site (wall, frame, etc.), to avoid the risk of overturning of the unit
due to external causes (accidental collision, earthquake, etc.).
Wall fastening screws not supplied.
Sizes in millimetres
UM_w-MEXT_01_Z_10_20_ML
Size
F1
F2
A
mm
520
920
420
420
B
mm
90
90
C
mm
View from the bottom
F2
920
420
2.2.4

CONDENSATE TANK (UNDER VERSION)

Additional Under version peraluman collection tank.
This component must be treated as a safety device, installed in the floor under the machine,
to collect any water leaks.
The water sensor must be installed by the installer in the collection tank
The tank has a Ø 22mm drain.
Sizes in millimetres
2.2.5

FREE SPACE AROUND THE INSTALLATION

OBLIGATION
The correct installation of the machine requires compliance with
the clearances shown in the figure. This allows ease of access to
the components of the machine for the purpose of normal
inspection and maintenance operations.
Units may be installed side by side.
Internal access is at the front for all sizes (F1, F2).
UNDER
850
Sizes in millimetres
OVER
850
Sizes in millimetres
22
TRANSLATION OF THE ORIGINAL INSTRUCTIONS
English
Collection tank with water
sensor
850