5.1
Acknowledge alarm
The control unit displays (alarm) messages as follows:
the alarm LED flashes red
an error message appears in the display,
an acoustic signal
Press acknowledge alarm button for 1 second.
Acoustic signal is muted, LED stops flashing.
5.2
To put into service, proceed as follows:
CAUTION
If the control unit is used as a redundant control unit,
to fulfil its function it must be connected via an elec-
tric circuit separate from the hybrid lifting station.
Plug in the mains plug.
All LEDs light up, one after the other.
|Menu 0 System info|
Check whether
(Indicates a successful system test.)
Power LED (green) indicates standby state (ready for
operation).
If the control unit has not yet been initialised it starts the
initialisation automatically.
40 / 148
appears.