9. Troubleshooting

The infrared control unit is equipped with diagnostic software which monitors the
system status when switching on and during operation. As soon as the diagnostic
software identifies an error, the infrared control unit switches the heating system off.
Error
E1
E3
E4
E5
E6
E7
► If the error still persists despite performing the measures described
Downloaded from
www.Manualslib.com
Description
S a f e t y t e m p e r a t u r e
limiter
Room sensor interruption
Room sensor short-
circuit
Foil sensor interruption
Foil sensor short-circuit
Foil excess temperature
above, please contact your supplier.
WORLD OF WELLNESS
manuals search engine
Cause / rectification
The sensor included in the delivery does
not have a safety temperature limiter.
Check that the ex-works wire jumper is
secure.
Check the cabin sensor cable for dam-
age and that the terminal points are con-
nected properly
Check the cabin sensor cable for dam-
age.
If you are not using foils or heating plates,
the ex-works dummy sensor must stay
in position.
If you are using a foil sensor, check the
cable for damage and check that the ter-
minals are connected properly.
If you are using a foil sensor, check the
cable for damage and check that the ter-
minals are connected properly.
If you are not using foils or heating plates,
the ex-works dummy sensor must stay
in position.
If you are using a foil sensor, check the
cable for damage and check that the ter-
minals are connected properly.
p. 21/22