Kessel Aqualift F Basic Einbau- Und Betriebsanleitung Seite 33

Inhaltsverzeichnis

Werbung

Verfügbare Sprachen
  • DE

Verfügbare Sprachen

  • DEUTSCH, seite 1
Operating states
LED
Green
Red
Orange
orange
(1)
(2)
(3)
Potential-free contact is activated (Art.No. 80074 must have been activated and connected beforehand)
1
The battery monitoring is only active if a battery was connected at the time of commissioning.
2
Alarm statuses / errors
LED
Green
Red
Orange
orange
(1)
(2)
(3)
Potential-free contact is activated (Art.No. 80074 must have been activated and connected beforehand)
1
The battery monitoring is only active if a battery was connected at the time of commissioning.
2
If the error re-occurs, contact customer service
3
Acknowledge alarm
If a condition arises that triggers an alarm, this will be indicated through the illumination of the alarm LED (2) and, if applic-
able, one of the other LEDs. After rectifying the cause of the alarm, the alarm can be acknowledged by pressing the button
(7).
Switching off the alarm tone
Press button (7) 1x
Acknowledge alarm
Press and hold button (7) > 3 seconds.
The alarm indicator goes out, the alarm is acknowledged.
010-974
Acoustic
signal
PFC
(interval)
(4)/(5)
-
-
-
-
-
-
-
-
-
-
Acoustic
signal
PFC
(interval)
(4)/(5)
Yes
-
Yes
Yes
-
-
Yes
Lifting station/Installation and operating instructions
Description
1
Power outage, no
battery monitoring
Ready for operation
System tank full, will
be pumped out shortly
Pumping sys-
tem tank to empty
Maximum switch-
ing cycles exceeded
Description
1
Battery error
2
Power outage, mains voltage
failed, system non-functional
Level error, illogical
sequence of levels detected
Max. number of runs/run-
time; wastewater pump was
switched on too often/too long
Alarm level exceeded
Maximum switch-
ing cycles exceeded
Measure
Restore the mains voltage
2
-
No action required, waste-
water pump can be switched
off with button (8) (see
"Manual operation")
Acknowledge alarm
and replace control unit
Measure
Replace battery
Reinstate mains volt-
age, acknowledge alarm
Acknowledge alarm
Wait until the level drops
below the alarm level again
Acknowledge alarm
and replace control unit
3
33 / 112