WHERE TO INSTALL THE PANEL:
It is good practice to install the panel correctly, taking particular care to comply with the following indications.
the panel must be kept in a completely dry place, far from sources of heat;
the electric panel must be perfectly closed and isolated from the outside environment, so as to avoid the entry of insects, humidity and dust
which could damage the electrical components, jeopardising their regular operation.
Choose the sensors with a grade of protection suitable for the place in which they will be positioned.
1.1

Technical characteristics

Power supply
+10% - 15%
Frequency
Grade of protection
No. pumps that can be connected:
Maximum rated current of the pumps
Maximum rated power of the pumps
Environment temperature
Storage temperature
Air relative humidity
Max. altitude:
1.2

Protections

The panel is self-protected and protects the electropumps against:
overloads and excess temperature with automatic reset,
short circuits with fuses (only Plus model),
excess currents in pumps (overload protection),
abnormal voltages,
lack of phase and thermal protection KK,
dry operation,
rapid starts,
faults of the pressure sensor,
inconsistency of floats and/or probes,
blocking of the pumps.
2

INSTALLATION

Strictly respect the electric supply values indicated on the electrical data plate.
Although it has a grade of protection IP55, it is not advisable to use it in an atmosphere charged with oxidising or corrosive
gases.
The panels must be protected against the direct rays of the sun and against unfavourable weather conditions.
Use good quality cables with a section suitable for the current required by their motors and for their length. Pay particular
attention to the power cable which must carry the current for all the pipes connected.
The sensors must be suitable for the place in which they are positioned.
It is necessary to take suitable steps to keep the temperature inside the panel within the "limits of environment temperature
use" listed below.
High temperatures can lead to accelerated ageing of all the components, resulting in more or less severe malfunctions.
It is also recommended that the person carrying out installation should ensure the cable clamps are watertight.
Accurately tighten the cable clamps where the power cable enters the panel and those of any external controls, connected
by the installer, so as to ensure that the cables cannot work loose from the clamps.
ENGLISH
E.box Plus
E.box Plus D
3 x 400V
3 x 230 V
1 x 230V
50/60Hz
IP 55
1 or 2
12A
5.5kW at 3 x 400V
3.2kW at 3 x 230V
2.2kW at 1x230V
-10 ÷ 40°C
-25°C ÷ 55°C
50% at 40°C
90% at 20℃
1000 m (a.s.l.)

Table 1: Technical data

65
E.box Basic
E.box Basic D
1 x 230V
50/60Hz
IP55
1 or 2
12A
2.2kW at 1 x 230V
10 ÷ 40°C
-25°C ÷ 55°C
50% at 40℃
90% at 20℃
1000 m (a.s.l.)