Herunterladen Inhalt Inhalt Diese Seite drucken

Table 17: General Table Of Alarms: Signals And Contacts; Table 18: Digital Inputs R And N Protection /Alarm - DAB E.Box Plus Installations- Und Wartungsanleitungen

Inhaltsverzeichnis

Werbung

Verfügbare Sprachen
  • DE

Verfügbare Sprachen

  • DEUTSCH, seite 177
Voltage selector error
alarm
Voltage error alarm
Internal error alarm
General alarm pump
P1+P2
Indicates the number of blinks made by the warning led
Led lit with fixed light
*
The alarm may occur up to a maximum of 6 times in 24 hours, after which it becomes blocking.
**
If malfunctions/alarms occur on both pumps at the same time, the REMOTE ALARM (relays Q1, Q2, Q3) is activated and the
GENERAL ALARM (red) is lit with a fixed light.
***
In KIWA pressure boosting mode the error is not self-resetting and must be reset manually.
Self-resetting alarm =
Blocking alarm =
10.2
Digital inputs R and N protection /alarm
Digital inputs
Pressure boosting and KIWA
pressure boosting function
The 2 pumps stop with:
R
- general alarm signal,
- Q3 remote signal
The 2 pumps stop with:
- general alarm signal,
- alarm signal against dry running.
- Q3 remote signal
N
Attention! if terminals R and N are not
used they must be jumpered!

Table 17: General table of alarms: signals and contacts

The E.Box reactivates the pump if the cause that generated the alarm is removed, or, in cases where this is not
possible, it makes attempts at intervals of time.
The E.Box keeps the pump stopped until a manual reset is carried out.
Max. Pressure
Min. Pressure

Table 18: Digital inputs R and N protection /alarm

ENGLISH
Filling function
Min. Level (in tank)
The 2 pumps start with:
- general alarm signal,
- Q3 remote signal
Tripping and reset after 0.5 seconds.
Max. level (in tank)
The 2 pumps stop with:
- general alarm signal,
- Q3 remote signal
Min. Level (water reserve)
The 2 pumps stop with:
- general alarm signal,
- signal against dry running.
- Q3 remote signal
Tripping and reset after 1 second.
Attention! if terminal N is not used it must
be jumpered! If level probes are used,
only R must be jumpered, if it is not
used.
110
X
X
X
X
X
X
Draining function
Max. level
The 2 pumps start with:
- general alarm signal,
- Q3 remote signal
Tripping and reset after 0.5 seconds.
Min. Level
The 2 pumps stop with:
- general alarm signal,
- alarm signal against dry running,
- Q3 remote signal
Tripping and reset after 1 second.
Attention! if terminal N is not used it must
be jumpered!
X
X
X
X

Werbung

Inhaltsverzeichnis
loading

Diese Anleitung auch für:

E.box plus dE.box basicE.box basic d

Inhaltsverzeichnis