FF: Fault log display

Chronological display of the faults that have occurred during system operation.
For each fault the following are displayed:
A symbol for the area concerned: the panel, pump P1 or pump P2.
The type of error or alarm, summed up in a code. See Table 19).
The number of times the error has occurred.
A text description of the error or alarm.
The time of switching on the panel or of pump operation at which the error occurred.
The order of the error in the log and the number of errors in the memory.
The faults are displayed in chronological order starting from the oldest one. The last one that occurred is shown first. The maximum number of
faults that can be displayed is 64; if the number of errors is greater, the oldest ones are overwritten.

CT: Display contrast

Adjusts the display contrast.

LA: Language

Changes the language used on the display. Attention, Kiwa mode is present only if the language is Dutch, French or English UK and US.
Note: If US is selected, the E.Box will use English with Imperial measurements.

HS: System operating hours

Indicates the hours the system has been on.

H1: Pump P1 operating hours

Indicates the hours the pump P1 has been on.

H2: Pump P2 operating hours

Indicates the hours the pump P2 has been on.

9.4.3 SETPOINT MENU

From the main menu, hold down simultaneously the "MODE" and "SET" keys until "SETPOINT MENU" appears on the display (or use the selection
menu pressing "+" or "-"). In this menu the parameters displayed depend on the type of application.
SP: Setting the Set Point pressure (only in pressure boosting and in KIWA pressure boosting with

pressure sensor)

Pressure Set Point at which the E.Box keeps the plant under pressure. It can vary between 1 bar (14 psi) and the full-scale value of the sensor
minus 2 bar (28 psi).
RP: Setting the Pressure Differential (only in pressure boosting and in KIWA pressure boosting

with pressure sensor)

Pressure differential in which the E.Box panel maintains the pressure in the plant. See chapter on pressure boosting.
It can vary between 5% and 95% of SP. SP + RP cannot exceed the full-scale value of the sensor. See chapter on pressure boosting.

HC: Pump P2 starting level (only in drainage or filling with depth sensor)

Starting level of pump P2.
HB: Pump P1 starting level (only in drainage or filling with depth sensor)
Starting level of pump P1.
HA: Pumps stopping level (only in drainage or filling with depth sensor)
Stopping level of pumps P1 and P2.

9.4.4 INSTALLER MENU

From the main menu, hold down simultaneously the "MODE" and "SET" keys until "INSTALLER MENU" appears on the display (or use the
selection menu pressing "+" or "-"). The menu allows you to view and modify various configuration parameters: the MODE key allows you to scroll
through the menu pages, the "+" and "-" keys allow you respectively to increase and decrease the value of the parameter concerned. Press SET
to leave this menu and return to the main menu.
ENGLISH

Figure 59: Errors in the memory