Device installation
4.2.2
Control inputs and outputs EMP KKS / II / III
4.2.2.1 EMP KKS / II / III Overview
EMP KKS & EMP II
I
III
II
4.2.2.2 EMP KKS / II / III Connector assignments of Slot I (3-terminal)
Input for low-level advance warning and empty report
3
1
4
4.2.2.3 EMP KKS / II / III Connector assignment of slot II (5-terminal)
Input for pulse signal, standard signal, metering lock, batch and metering
monitoring
2
1
3
5
4
4.2.2.4 EMP KKS / II / III Connector assignments of slot III (4-terminal)
Output for low-level warning, empty report, alarm, stroke signal
2
3
1
4
MAN033535 Rev. 06-04.2020
EMP III
I
III
Pin Conductor
Assignment
coloring
1
brown
Input low-level warning
3
blue
Input empty report
4
black
GND (┴)
Conductor
Pin
Assignment
coloring
1
brown
Output 5 V, DC (loadable with max. 50 mA)
2
white
Pulse input (also as configurable batch / metering monitoring)
3
blue
Metering lock (also as configurable batch / metering monitoring)
4
black
GND (┴)
5
grey
Input standard signal 0/4...20 mA
Conductor
Pin
Assignment
coloring
1
brown
Output low-level warning, empty report and fault (+)
2
white
Output low-level warning, empty report and fault (-)
3
blue
Output stroke signal (+)
4
black
Output stroke signal (-)
Input for low-level advance warning
IV
I
II
and empty report
Input for pulse- / standard signal and
II
metering lock, batch pulse, metering
monitoring
Output for low-level advance warning,
III
empty report, alarm, stroke signal
Input for diaphragm breakage
IV
monitoring