ALARMS
This control governs two types of alarms:
 S erious Alarms: cause the forced switching off of the ther-
mostat
 N on-serious Alarms: do not cause the forced switching off
of the thermostat, but disable possible critical functions
SERIOUS ALARMS
Alarm code
 C ode A01= error of external air temperature sensor (in
case of on-board thermostat)
 C ode A02 = error of internal air temperature sensor (in case
of wall mounted thermostat and disconnected external air
temperature sensor)
NON-SERIOUS ALARMS
THERMOSTAT OFF
THERMOSTAT ON
 Code A03 = water sensor error
 Code A04 = external humidity probe error (only if a remote
temperature probe is installed)
 Code A05 = internal humidity probe error
N.B.: the alarm code is displayed only when the
thermostat is switched off
Installation and user manual
14
MODBUS
The protocol implemented in the controller is Modbus RTU
(9600, N, 8, 2) on RS485.
FUNCTIONS IMPLEMENTED
 0 x03 : Read Holding Registers
 0 x04 : Read Input Registers
 0 x10 : Write Multiple registers
EXCEPTIONS IMPLEMENTED
Exception Code 02: Invalidate data address
LIST OF SUPERVISION PARAMETERS
ADDRESS
REGISTER
0
Status
1
Speed
2
Air temperature
3
Humidity
4
Water temperature
5
P00: Configuration
6
P05: DIN Config.
7
T. Active setpoint
8
T. User setpoint
9
LCD version
10
P09: DOUT1 Config.
11
P10: DOUT1 Logic
12
P11: DOUT2 Config.
13
P12: DOUT2 Logic
14
P14: AOUT1/2 Config.
15
analog output 1
16
analog output 2
50
Digital 1
51
Hourly programming
52
Setpoint - Cooling
53
Setpoint - Heating
54
Minimum Setpoint – Cool.
55
Maximum Setpoint – Cool.
56
Minimum Setpoint – Heat.
57
Maximum Setpoint – Heat.
58
Speed
59
Economy Correction
60
Modulating fan mode
TYPE
U.of.M.
R
-
R
-
R
[°C/10]
R
%
R
[°C/10]
R
-
R
-
R
[°C/10]
R
[°C/10]
R
-
R
R
R
R
R
R
[%]
R
[%]
R/W
-
R/W
-
R/W
[°C/10]
R/W
[°C/10]
R/W
[°C/10]
R/W
[°C/10]
R/W
[°C/10]
R/W
[°C/10]
R/W
-
R/W
[°C/10]
R/W
-