10.4.6 Set the measured value damping
► Select [dAP] and set the damping constant in seconds
(Ƭvalue 63 %): 0...5 s (→ 4.8).
10.4.7 Setting the switching delays
► Select [dSx] and set the delay for switching OUTx in seconds: 0���60 s�
► Select [drx] and set the delay for resetting OUTx in seconds: 0���60 s�
10.4.8 Set output status in fault condition
► Select [FOU1] or [FOU2] and set the value:
1� Switching output:
- On = output 1 / output 2 switches ON in case of an error�
- OFF = output 1 / output 2 switches OFF in case of an error�
- OU = output 1 / output 2 switches irrespective of the fault as defined
with the parameters�
2� Frequency output:
- On = frequency signal: 130 % of FrP1 / FrP2 (→ 4.7).
- OFF = frequency signal: 0 Hz (→ 4.7)�
- OU = frequency signal output continues to run without changes�
3� Analogue output:
- On = the analogue signal goes to the upper fault value (→ 4.6).
- OFF = the analogue value goes to the lower fault value (→ 4.6).
- OU = the analogue signal corresponds to the measured value�
10.4.9 Calibration of the curve of measured values
► Select [CGA] and set a percentage between 60 and 140 → 4.4.
(100 % = factory calibration)
[CGA] is only available if the operating mode GAS or LIQU is
selected�
Menu CFG:
[dAP]
Menu DIS:
[dS1]
[dS2]
[dr1]
UK
[dr2]
Menu CFG:
[FOU1]
[FOU2]
Menu INI:
[CGA]
75