10.2.7 Configure the analogue output for flow for OUT2
► Select [SEL2] and set FLOW�
► Select [ou2] and set the function:
I = flow-proportional current signal 4...20 mA
► Select [ASP2] and set the flow value at which the output signal is 4 mA�
► Select [AEP2] and set the flow value at which the output signal is 20 mA�
[ASP2] and [AEP2] are only available if the operating mode GAS or
LIQU is selected�
10.2.8 Carry out the flow adjustment
1� High-flow adjustment:
► Switch on the supply voltage�
► Activate the maximum flow in the installation�
► Select [t�HGH] and press [●]�
> [tch] is displayed�
► Keep [▲] or [▼] pressed.
> [----] is displayed�
► Briefly press [●]�
> Display [donE]: adjustment successful�
Display [FAIL]: Repeat the adjustment�
> The unit defines the existing flow as maximum flow (final value of the
measuring range = 100 %)�
► Briefly press [●]�
2� Low-flow adjustment:
► Switch on the supply voltage�
► Activate the minimum flow in the installation�
► Select [t�LOW] and press [●]�
> [tch] is displayed�
► Keep [▲] or [▼] pressed.
> [----] is displayed�
► Briefly press [●]�
> Display [donE]: adjustment successful�
Display [FAIL]: Repeat the adjustment�
> The unit defines the existing flow as minimum flow (0 %)�
► Briefly press [●]�
[t�HGH] and [t�LOW] are only available if the operating mode REL is
selected�