CONNECTIONS
NTC/PTC - 15A (12Va/c)
ALL
OUT
1
2
3
4
5
7
Supply
NTC/PTC - 15A (230Va)
ALL
OUT
1
2
3
4
5
6
7
Supply
1-2
N.O. alarm relay ALL
1-3
N.C. alarm relay ALL
4-5
N.O. regulator relay OUT
A
TTL input for Copy Card and TelevisSystem connection
NTC/PTC MODEL - 15A
Display range:
Analogue input
8
10 11
12
Serial
Digital outputs
Buzzer output
Measurement range
Accuracy
10 11
12
Resolution
INPUT/OUTPUT CHARACTERISTICS
NTC: -50...110°C (-58...230°F)
PTC: -50...140°C (-58...302°F)
on display with 3½ digits + sign
1 NTC or 1 PTC
(selectable by parameter H00)
TTL for connection to Copy Card or
Televis/Modbus remote control systems
ALL: 1 SPDT relay 8(4)A 250 V
OUT: 1 SPST relay 15A 250 V
only on models where this is provided
-50 ... 140°C (-58 ... 284°F)
better than 0.5% of end of scale +1 digit
0.1°C (0.1°F up to +199.9°F; 1°F over)
TERMINALS
*6-7
Power supply 230V
*7-8
Power supply 12V
10-11
Probe Pb1 Input
* depends on model