PAR. DESCRIPTION
Controller 1 switch-on time in the event of faulty probe.
On1
if On1=1 and OF1=0, the controller remains on;
if On1=1 and OF1>0, the controller operates in Duty Cycle mode.
Controller 1 switch-off time in the event of faulty probe.
OF1
if OF1=1 and On1=0, the controller remains off;
if OF1=1 and On1>0, the controller operates in Duty Cycle mode.
ALARMs (folder 'AL')
Parameters 'HA1' and 'LA1' , intended as the absolute temperature value or
Att
differential in relation to the setpoint.
AbS (0) = absolute value; rEL (1) = relative value.
AFd Alarm differential.
PAO Alarm override time after device is switched on following a power failure.
Alarm exclusion time until the Setpoint is reached.
SAO
0 = disabled. If SAO >0, an alarm will be generated if the Setpoint is not
reached after the time SAO (in hours).
tAO Delay preceding indication of temperature alarm.
Alarm output polarity. nC (0) = alarm active and output disabled
AOP
nO (1) = alarm active and output enabled
tP
Enable all keys to acknowledge an alarm. n (0) = no; y (1) = yes.
COMMUNICATION (folder 'Add')
PtS Selection of communication protocol. t = Televis; d = Modbus.
dEA Index of the device within the family (valid values from 0 to 14).
FAA Device family (valid values from 0 to 14).
Adr Modbus protocol controller address.
MODEL
ALL
ALL
ALL
ALL
ALL
ALL
ALL
ALL
ALL
ALL
ALL
ALL
ALL
20
RANGE
VALUE M.U. LEVEL
0...250
0
min
0...250
1
min
AbS/rEL
AbS
flag
1.0...50.0
2.0
°C/°F
0...10
0
hours
0...10
0
hours
0...250
0
min
nC/nO
nC
flag
n/y
y
flag
t/d
t
flag
0...14
0
num
0...14
0
num
1...255
1
num
Inst
Inst
Inst
Inst
Inst
Inst
Inst
Inst
Inst
Inst
Inst
Inst
Inst