PAR. DESCRIPTION
CONFIGURATION (folder 'CnF')
Probe type selection.
H00
• NTC/PTC: Ptc (0) = PTC, ntC (1) = NTC
• PT100-Tc: Jtc (0) = TcJ, Htc (1) = Tck; Pt1 (2) = PT100.
Press the ESC, UP and DOWN keys (if configured for a second function) for the
H02
time H02 to activate the function itself.
Window filter:
H05
-2 = very fast; -1 = fast; 0 = normal; 1 = slow; 2 = very slow.
Stand-by operating mode.
0 = only display switches off;
H08
1 = display on and controllers locked;
2 = display off and controllers locked.
Delay for output activation after Power On. If H10 = 0 the delay is NOT active; if
H10
H10 ≠ 0 the output will not be activated before this time has expired.
Configuration of UP key.
H31
0 = disabled; 1 = not used; 2 = Offset setpoint; 3 = Outputs stopped;
4 = not used; 5 = not used; 6 = Stand-by; 7 = not used.
H32 Configuration of DOWN key. Same as H31.
H33 Configuration of ESC key. Same as H31.
rEL firmware version. Device software release: read-only parameter.
tAb Parameters table. Reserved: read-only parameter.
If one or more parameters are changed, the controller MUST be switched off and switched on again.
22
MODEL
RANGE
VALUE M.U. LEVEL
NTC/PTC
Ptc/ntC
PT100-Tc
Jtc/Htc/Pt1
ALL
0...15
ALL
-2/-1/0/1/2
ALL
0/1/2
ALL
0...250
ALL
0...7
ALL
0...7
ALL
0...7
ALL
/
ALL
/
ntc
flag
User/Inst
Jtc
num
5
secs
Inst
0
num
Inst
2
num
Inst
0
min
Inst
0
num
Inst
0
num
Inst
6
num
Inst
/
/
User/Inst
/
/
User

Quicklinks ausblenden:

Werbung

Inhaltsverzeichnis
loading

Inhaltsverzeichnis