CONNECTIONS
NTC/PTC (12Va/c, 12-24Va/12-36Vc)
OUT
ALL
1
2
3
4
5
7
8
Supply
NTC/PTC (24Va, 230Va)
OUT
ALL
1
2
3
4
5
6
7
Supply
1-2
N.O. regulator relay OUT
1-3
N.C. regulator relay OUT
4-5
N.A. alarm relay ALL
A
TTL input for Copy Card and TelevisSystem connection
NTC/PTC MODEL
Display range:
Analogue input
9 10 11
Serial
Digital outputs
Buzzer output
Measurement range
Accuracy
9 10 11
Resolution
TERMINALS
INPUT/OUTPUT CHARACTERISTICS
NTC: -50...110°C (-58...230°F)
PTC: -50...140°C (-58...302°F)
on display with 3½ digits + sign
1 NTC or 1 PTC
(selectable by parameter H00)
TTL for connection to Copy Card or
Televis/Modbus remote control systems
OUT: 1 SPDT relay 8(4)A 250 V
ALL: 1 SPST relay 8(4)A 250 V
only on models where this is provided
-50 ... 140°C (-58 ... 284°F)
better than 0.5% of end of scale +1 digit
0.1°C (0.1°F up to +199.9°F; 1°F over)
*6-7
Power supply 24V
*7-8
Power supply 12V
9-11
Probe Pb1 Input
* depends on model
6
a
a
and 230V
.
a
a
and 12-24V
12-36V
a/c
a/
c