Tabulating the results for each detector position we get:
Detector
N=1
N=2
N=3
N=4
N=5
N=6
N=7
N=8
N=9
N=10
N=11
N=12
N=13
N=14
N=15
N=16
N=17
N=18
N=19
N=20
N=21
N=22
Power Supply
So 22 detectors just exceeds the power supply guarantee voltage, therefore the answer
for a safe maximum number of detectors is 21.
If this is not a convenient solution then there is scope for increasing the number by
changing the power supply or using thicker (lower resistance) cable.
22
Voltage at
Detector (V)
10
10.03388
10.10164
10.20328
10.3388
10.5082
10.71148
10.94864
11.21968
11.5246
11.8634
12.23608
12.64264
13.08308
13.5574
14.0656
14.60768
15.18364
15.79348
16.4372
17.1148
17.82628
18.57164
Cable current (A)
0.070
0.14
0.21
0.28
0.35
0.42
0.49
0.56
0.63
0.7
0.77
0.84
0.91
0.98
1.05
1.12
1.19
1.26
1.33
1.4
1.47
1.54
Xgard Bright
Cable voltage
drop (V)
0.03388
0.06776
0.10164
0.13552
0.1694
0.20328
0.23716
0.27104
0.30492
0.3388
0.37268
0.40656
0.44044
0.47432
0.5082
0.54208
0.57596
0.60984
0.64372
0.6776
0.71148
0.74536

Werbung