• The lid on Xgard Bright must be kept tightly closed until power to the detector is
isolated otherwise ignition of a flammable atmosphere can occur. Before removing
the cover for maintenance, ensure the surrounding atmosphere is free of flammable
gases or vapours.

General safety information

• Xgard Bright gas detectors must be installed, operated and maintained in strict
accordance with these instructions, warnings, label information, and within the
limitations stated.
• Xgard Bright detectors are designed to detect gases or vapours in air, and not
inert or oxygen deficient atmospheres. Xgard Bright oxygen detectors can mea-
sure in oxygen deficient atmospheres.
• Electrochemical cells used in toxic and oxygen versions of Xgard Bright contain
small volumes of corrosive electrolyte. Care should be observed when replacing
cells to ensure that the electrolyte does not come into contact with skin or eyes.
• Maintenance and calibration operations must only be performed by qualified ser-
vice personnel.
• Only genuine Crowcon replacement parts must be used, substitute components
may invalidate the certification and warranty of the detector.
• Xgard Bright detectors must be protected from extreme vibration, and direct sun-
light in hot environments as this may cause the temperature of the detector to rise
above its specified limits and cause premature failure. A sunshade is available for
Xgard Bright.
• This equipment must not be used in a Carbon Disulphide atmosphere.

2.3 Storage instructions

Some types of sensor available with Xgard Bright have limited life when left un-
powered and/or may be adversely affected by temperature extremes or environmental
contamination. Ideal storage conditions are 20˚C and 60%RH. Do not expose sensors
to contaminants such as silicones, lead compounds and strong solvents such as isopro-
panol. It is strongly recommended detectors are installed and powered within 3 months
of purchase.