Operation with DiagMonitor monitoring software
Installing DiagMonitor
If your device uses the "A1 image" (see "PCS 7 software product package (Page 20)"), you can install the DiagMonitor
monitoring software as follows.
Procedure
1. Insert the first Restore DVD into your device.
2. Navigate to the "Additional_Products" folder and open the version-specific DiagMonitor folder.
3. Run the following files:
–
DiagMonitor_Silent_Install.bat
–
CM_Activate.exe
The DiagMonitor monitoring software is installed.
4. Reboot the computer.
5. Configure the SNMP service. You will find information on this in the section: "Configuring SNMP service (Page 30)".
6. Now configure the monitoring functions of DiagMonitor. You can find information about this in the section "Configuring
monitoring functions (Page 31)".
Configuring SNMP service
SNMP service is installed on your computer. It is preset in such a way that SNMP packets are accepted from any host. You
can change this setting.
Procedure
1. Open the administration tool for the services of your system.
2. Double-click "SNMP Service'".
The "Properties" windows opens.
3. Select the "Security" tab.
4. Select one of the following options:
–
Accept SNMP packets from any host
No further settings are required here.
–
Accept SNMP packets from these hosts.
For the station to be monitored, enter the local address or the local computer name and the address of the
maintenance server (both addresses for a redundant MS server).
On the Maintenance Station, enter the local address or local computer name.
5. Under "Accepted community names", enter the name used in the configuration with read/write permissions.
6. Confirm your entries.