Once the failing safety device is repaired, in automatic after 1 second, all standard
commands that were selected, such as step by step, automatic mode, radio commands
and automatic closing start functioning again.
Note 1: during this functioning in dead man mode, in case of damage to the safety
strips (or photocells) the photocells (or safety strips) still work by interrupting the
operation in progress.
Note 2: the stop command is not to be considered a safety command that can be
bypassed in this mode. Therefore, when pressed or damaged, it will not allow
any movement of the gate.
The dead-man operation is only an emergency operation which must be activated
for a very short period and with the complete installation at sight so to have a
secure and safe control of the system. As soon as possible however, the failing
safety devices must be repaired and activated.
FLASHING LIGHT
Connect the flashing light to J1 flashing light outputs, use flashing lights ACG7059 and
bulbs of 40W maximum.
NOTE: This electronic K board can only supply power to FLASHING LIGHTS with inbuilt
flashing circuit.
PRE-FLASHING function
The DIP8 in the ON position enables the pre-flashing, the FLASHING LIGHT starts working
3 seconds before every movement of the gate.
The DIP8 in the OFF position disables any pre-flashing, the FLASHING LIGHT and the
motor will star at the same time.
OPEN GATE INDICATOR (SIGNAL-COM)
It indicates the gate status: open, partially open or not completely closed.
It switches off only when the gate is completely closed.
During programming, this indicator is active.
NOTE: if button panels or bulbs are in excess, the electronic board logic will be impaired
and operations might stop.
T
ROUBLE SHOOTING
After having carried out all connections, by carefully following the layout and having positioned the gate in intermediate position, check the correct ignition of LEDS DL2, DL3, DL4, DL5, DL8.
In case of no ignition of the LEDS, always with gate in intermediate position, check the following and replace any faulty components.
DL2
switched off
Faulty Stop button
DL3
switched off
Faulty opening limit switch
DL4
switched off
Faulty closing limit switch
DL5
switched off
Faulty photocells
DL8
switched off
Faulty safety edge (In case the edge is not connected, carry out jumper between COM and EDGE)
During functioning with personnel present, with DIP 1 at ON, check that during opening the green DL6 LED switches on and that during closing the red DL7 LED switches on.
If not, invert clamps V and W on the motor terminal board.
After having carried out the various connections and having supplied voltage, all the
LEDS are switched off.
The gate opens but does not close after the time set.
The gate does not open or close by activating the various OPEN, CLOSE, K and RADIO
buttons.
By activating the K or CLOSE button the gate does not move.
FAULT
T
ECHNICAL SPECIFICATIONS
- Humidity
- Power voltage
- Frequency
- Maximum board absorption
- Interruptions in electricity supply
- Maximum load of open gate output
- Blinking unit maximum output load
- Current available for photocells and accessories
- Current available on radio connector
- ALL THE PUSH BUTTONS, INPUTS AND COMMANDS CONNECTED TO THE CONTROL
BOARD MUST BE CLE
Check the integrity of fuses F1 and F2. In case of interrupted fuse use only of
adequate value
F2 = 5A
Ensure to have set DIP 3 at ON.
Button K BUTTON always inserted in automatic functioning mode (DIP 6 OFF).
Replace button or switch of the selector switch.
Failed edge self-test => check the connections between electronic board and edge
feeder.
Attention: if not using a feeder for edges, DIP 12 must be at OFF position.
Faulty safety edge contact.
Faulty photocells contact with DIP 4 OFF.
Fix or replace the relative contact.
Impulse K or CLOSE always inserted.
Check and replace any buttons or micro-switches of the selector switch.
32
32
< 95% without condensation
400 Vac 3/PHASE
50/60Hz
30mA
100ms
3 W (equal to 1 3W bulb or to 5
LEDs connected in series through
a resistor of from 2.2 kΩ)
230 VAC 40W with resistive load
400mA 24Vdc
200mA 24Vdc
SOLUTION
F1 = 100mA.