- SETTINGS
DIP 1
MOTOR ROTATION DIRECTION CHECK (See Point C)
DIP 2
PROGRAMMING (See Point D)
DIP 2-1 PROGRAMMING OF PEDESTRIAN OPENING (See Point E)
DIP 3
ON - Automatic Closing ENABLED
OFF - Automatic Closing DISABLED
DIP 4
ON - Radio receiver STEP BY STEP
OFF - Radio receiver AUTOMATIC
DIP 5
ON - STEP BY STEP
Single pulse contact (K BUTT)
Pedestrian button (PED BUTT)
OFF - AUTOMATIC
Single pulse contact (K BUTT)
Pedestrian button (PED BUTT)
DIP 6
ON - Photocells active only in closing
OFF - Photocells always active
DIP 7
ON - Encoder enabled for PLUS operator
OFF - Encoder disabled
DIP 8
ON - Blinker pre-flashing
OFF - Blinker normal flashing
DIP 9
ON - Low speed in approaching DISABLED
OFF - Low speed in approaching ENABLED
DIP 10
ON - Electronic brake ENABLED
OFF - Electronic brake DISABLED
DIP 11
ON - Gradual start ENABLED
OFF - Gradual start DISABLED
DIP 12
ON - Safety strip self test ENABLED
OFF - Safety strip self test DISABLED
DIP 13
ON - Motor operation control by external power relays. Encoder,
low speed in approaching, gradual start and electronic brake
features, low speed and torque regulator will be automatically
disabled regardless their dip-switches and trimmers position.
OFF - Standard motor operation control without power relays.
DIP 14
OFF
DIP 15
OFF
DIP 16
OFF
DIP 17
ON - close command after the transit through the photocell ENABLED
OFF - close command after the transit through the photocell DISABLED
DIP 18
OFF - Available for future implemen
LED WARNINGS
DL1 - programming activated (red)
DL2 - stop contact NC (red)
DL3 - open limit-switch contact (red)
DL4 - close limit-switch contact (red)
DL5 - photocell contact (NC) (red)
DL6 - gate opening (green)
DL7 - gate closing (red)
DL8 - safety strip contact (NC) (red)
DL9 - Encoder output state
FUSES
F1 T100mA
Fuse for accessories protection
F2 T5A
Power circuit protection fuse
RELAYS AND MOTOR CONTROL
K1 => Opening command
K2 => Closing command
K3 => Flashing light command
Q5 => TRIAC - Direction command for opening and closing
POINT C
- MOTOR ROTATION DIRECTION CHECK
This operation is meant to help the installer during the installation and for further future
controls.
1 - Unlock the operator with the Manual Release, slide the leaf open about halfway and
lock the operator again.
2 - Turn DIP1 to ON position, LED DL1 starts blinking
3 - Press and hold the PROG.Button, the gate will open or close. Release the button and
the gate will stop. Press and hold again, the gate will move in the opposite direction.
The S1 control board has two movement leds
- DL6 the GREEN led for OPENING
- DL7 the RED led for CLOSING
When you press and hold the PROG.Button, if the gate opens with the green led on
then you may proceed to step 4.
If the gate moves in the wrong direction compared with the movement leds:
- turn OFF the main AC power
- reverse the V and W motor cables position (the blue motor cable must be always in
the U position)
- reverse the limit switch wires marked LSO and LSC
- turn ON the main AC power and check again the motor direction
4 - Turn DIP1 to OFF, the RED led DL1 will stop blinking.
During Point C procedure, safety devices (photocells and safety strip), stop button
and encoder input are not active.
(#) In Point D and Point E procedures, all of them will be active, so they must be
properly installed and connected to the control board. Any changing of the safety devices
input state, will stop the Point D and Point E procedure that must be repeated from the
beginning.
POINT D
- PROGRAMMING (#)
1 - The gate must be fully closed.
2 - Turn DIP2 to ON position, LED DL1 starts blinking
3 - Press PROG.Button, motor opens.
4 - Once reached the open position, the open limit switch will cut out motor and the gate
travelling will be stored. The gap of time between now (stop of motor) and the next
pressing of the PROG.Button (see step 5 below) will be then stored as waiting time
for Automatic Closing feature.
5 - Press PROG.Button, gate closes and the Automatic Closing time is stored (see DIP3
function to enable or disable the Automatic Closing feature).
6 - The LED DL1 will turn OFF, signalling exit from the Point D procedure.
Closing of the gate will be carried out at normal speed and only on approaching total
closing at low speed (depending on the adjustment of LOW SPEED trimmer).
7 - When the gate leaf reaches the close limit switch plate, the motor stops.
8 - Turn DIP2 to OFF position.
POINT E
- PROGRAMMING OF PEDESTRIAN OPENING (#)
1 - The gate must be fully closed.
2 - Turn DIP2 to ON position, the LED DL1 starts blinking quickly
3 - Immediately, turn also DIP1 to ON position, the LED DL1 starts blinking slowly
4 - Press the pedestrian pushbutton PED.Button, the gate opens
5 - When the gate leaf is opened enough for the pedestrian crossing, press the pedestrian
pushbutton PED.Button to stop the travel (thus defining the opening stroke of the
motor). The gap of time between now (stop of the motor) and the next pressing of
the PROG.Button (see step 6 below) will be stored as waiting time for Pedestrian
Automatic Closing feature.
6 - Press the pedestrian pushbutton PED.Button, gate closes and the Pedestrian
Automatic Closing time is stored (see DIP3 function to enable or disable the Automatic
Closing feature).
7 - Turn DIP1 to OFF position
8 - Turn DIP2 to OFF position
F
UNCTIONING OF CONTROL ACCESSORIES
ATTENTION: ONLY IMPULSIVE COMMANDS HAVE TO BE CONNECTED.
Make sure that any other type of command accessories (e.g. mass detectors)
used on the installation are set in the IMPULSIVE mode, otherwise, the gate will
be operated even without the protection of the safety devices.
STEP BY STEP or AUTOMATIC commands (K BUTT, PED.Button)
DIP5 - ON
The K BUTT and PED.Button perform the step by step cyclic command
open-stop-close-open-stop-etc.
DIP5 - OFF The K BUTT and PED.Button perform the automatic command:
- the open command, if pressed with the gate completely closed
- the close command, if pressed with the gate completely opened
- no effect, if pressed during the gate opening
- the gate re-open, if pressed while the gate is closing
The K BUTT opens the gate completely, whereas the PED.Button opens the gate partially
as described in Point E.