Faults and Alarms
Number / Fault
Cause
F037
An analog input is taking place in operating
mode 4..20 mA and a wire break has
Analog input
occurred. The number of the analog input
concerned is shown in fault value (r949).
F038
During a parameter task, a voltage failure has
occurred on the board.
Voltage OFF during
parameter storage
F040
Incorrect operating status
AS internal
F041
A fault has occurred when storing the values in
the EEPROM.
EEPROM fault
F042
Calculating time problems
Calculating time
At least 10 failures of time slots T2, T3, T4 or
T5 (see also parameters r829.2 to r829.5)
F044
A fault has occurred during the softwiring of
binectors and connectors.
BICO manager fault
F045
A hardware fault has occurred when accessing
an option board
Opt. Board HW
F046
A fault has occurred during the transfer of
parameters to the gating unit processor.
Par. Task
F047
The calculating time in the gating unit
computer is not sufficient
Gating Calc Time
F048
The pulse frequency set in P340 is not
permissible.
Gating Pulse Freq
F049
The firmware versions on the CU have
different firmware release.
SW version
F050
Error when initializing the TSY board
TSY Init.
14-6
Counter-measure
Check the connection to
- Analog input 1 -X102:15, 16,
or -X101:9,10 (Compact PLUS).
- Analog input 2 -X102: 17, 18.
Check parameters
- P632 CU AnaIn Conf
- P634 CU AnaIn Smooth
- P631 CU AnaIn Offset
Re-enter the parameter. The number of the
parameter concerned can be seen in fault
value r949.
Replace CU (-A10), or replace the unit
(Compact PLUS type)
Replace CU (-A10), or replace the unit
(Compact PLUS)
Reduce the calculating time load:
- Increase P357 Sampling Time
- Calculate individual blocks in a slower
sampling time
Observe r829 CalcTimeHdroom.
Fault value r949:
>1000 : Fault during softwiring of connectors
>2000 : Fault during softwiring of binectors
- Voltage OFF and ON
- Factory setting and new parameterization
- Replace the board
- Replace CU (-A10), or replace the unit
(Compact PLUS)
- Check connection of the board subrack to the
option boards and replace if necessary.
Power the unit down and up again.
Replace CU (-A10), or replace the unit
(Compact PLUS type)
Replace CU (-A10), or replace the unit
(Compact PLUS)
In case of synchronous motors (P095 = 12):
Pulse frequency set too high (P340>2kHz).
Change P340 Pulse Frequency.
Use uniform firmware
Check:
- Whether the TSY is correctly inserted
6SE7087-6KD60
Operating Instructions
SIMOVERT MASTERDRIVES
04.2006
Siemens AG