ZErTIFIZIErUNG
• „Use 60/75°C Copper Conductors Only".
• "During the UL evaluation, only Risk of Electrical Shock and Risk of Fire aspects
• In order to comply with CSA C22.2 No. 14-2010 (cUL) following external Input
Table 1: External mains input chokes
Cat. No. Housing Input Voltage [V] Reactor Cat. No.
16G6
17G6
18G6
19G6
Table 2: Input fusing of inverter modules
Cat. No.
16G6
17G6
18G6
19G6
The voltage rating of the external fuse(s) shall be at least equal to the input voltage of
the inverter module.
Max Wire Size: 4 AWG, strip wire insulation at 10 mm.
For 19G6 inverter series: Use 75°C copper conductor only
were investigated. Functional Safety aspects were not evaluated"
Chokes need to be installed: See table 1 below !
E
480 / 3ph
E
480 / 3ph
E
480 / 3ph
E
480 / 3ph
Housing
Input Voltage
E
E
E
E
16DRB04–1000
17DRB04–1000
18DRB04–1000
19DRB04–1000
UL248 Fuse type RK5 or J
[V]
480 / 3ph
480 / 3ph
480 / 3ph
480 / 3ph
FLA
Inductance [mH]
3 x 27 A
0.847
3 x 34 A
0.667
3 x 40 A
0.560
3 x 52 A
0.467
maximum rating [A]
50
60
70
90
49