11.6.2 Warning messages

Code
Error
No.
E07
generator operation
E32
Undervoltage -module
intermediate circuit
E33
Overvoltage -module
intermediate circuit
E50
PLR communication
error
E51
Unauthorised pump
combination
11.6.3 Emergency operation - Heating
Code
Eorror
No.
E52
Master/slave
communication error
Pump switches from
controlled operation
to fixed characteristic
(de- pending on set
value, see Fig. 5)
If the malfunction cannot be removed, please consult your sanitary and heating specialist or WILO Customer Service.
48
Cause
Remedy
Flow drives the impeller
Check settings;check operation
=> electr. current is fed
of the unit
back into the mains
Voltage variations in
Check electronic installation
the mains
Voltage variations in
Check electronic installation
the mains
Interface, line faulty,
After 5 min changeover from PLR
cable faulty
mode to local mode control
Different pumps
Cause
Remedy
MP communication
Check cable
cable faulty
Error type
Error matrix
Error matrix
HV
AC
F
F
F
D
F
D
F
F
F
F
Error type
Error matrix
Error matrix
HV
AC
E
E

Quicklinks ausblenden: