System Set Up
2. When 2-zone temperature control is active or wireless remote controllers are
available, from Room RC zone select screen, select zone no. to assign to
each remote controller.
3. From Sensor setting screen, select a room sensor to be used for monitoring
the room temperature from Zone and Zone2 separately.
Control option
Corresponding initial settings room sensor
(pages 26 and 27)
Zone
A
Room RC-8 (one each
for Zone and Zone2)
B
TH
C
Main controller
D
*
* Not specified ( if a field-supplied room thermostat is used)
Room RC-8 (one each for Zone and Zone2) (if a wireless remote controller
is used as a room thermostat)
4. From Sensor setting screen, select Time/Zone to make it possible to use differ-
ent room sensors according to the time schedule set in the Select Time/Zone
menu. The room sensors can be switched up to 4 times within 24 hours .

Domestic Hot Water (DHW)/Legionella Prevention

The domestic hot water and legionella prevention menus control the operation of
DHW tank heat ups.
<DHW mode settings>
. Highlight the hot water icon and press CONFIRM.
2. Use button F to switch between Normal and ECO heating modes.
3. To edit the mode press F2 to display the HOT WATER (DHW) SETTING menu.
4. Use F2 and F3 keys to scroll through the menu selecting each component in
turn by pressing CONFIRM. See the table below for description of each setting.
5. Enter the desired number using the function keys and press CONFIRM.
Menu subtitle
Function
DHW max. temp
Desired temperature of stored hot water
DHW max. temperature
Difference in temperature between DHW max. temp and the temperature at which DHW mode restarts
drop
DHW max. operation time Max time allowed for stored water heating DHW mode
DHW mode restriction
The time period after DHW mode when space heating has priority over DHW mode temporarily pre-
venting further stored water heating
(Only when DHW max. operation time has passed.)
Zone2
*
*
*
*
Time/Zone schedule setting screen
Range
40 - 60
5 - 30
30 - 20
30 - 20
Unit
Default value
°C
50
°C
0
min
60
min
30
34