Hardware Settings - Endress+Hauser RID14 Anleitung

Field indicator with foundation fieldbus - protocol
Vorschau ausblenden Andere Handbücher für RID14:
Inhaltsverzeichnis

Werbung

Verfügbare Sprachen

Verfügbare Sprachen

Operating the field indicator
Process control systems
Honeywell PKS Experion
Yokogawa Centum CS3000
These can be used for configuring both the FF functions and all of the device-specific
parameters. The predefined function blocks allow uniform access to all the network and fieldbus
device data.
System files
You require the following files for commissioning and configuring the network:
• Commissioning → device description (DD: *.sym, *.ffo)
• Network configuration → CFF file (Common File Format)
A detailed step-by-step description of the procedure for commissioning the FF
functions is given in Section 6.3.1 in the Operating Instruction together with
information on configuring device-specific parameters.
6.5

Hardware settings

DIP switches inside the field indicator housing are used to enable and disable hardware write
protection. When write protection is active, parameters cannot be modified. The current write
protection status is displayed in the WRITE_LOCK parameter (Resource Block, see Section 11).
ESD - Electrostatic Discharge
Protect the terminals from electrostatic discharge. Failure to observe this may result
in destruction or malfunction of parts of the electronics.
To set the DIP switches, proceed as follows:
1.
Open the housing by removing the front cover.
2.
Remove the display.
3.
Configure the DIP switch on the electronics accordingly. Switch to ON = function enabled,
switch to OFF = function disabled.
4.
Close the housing front cover and secure it.