Wiring
5.2.2 Fieldbus connector
Optionally, a fieldbus connector can be installed in field housing instead of a cable gland.
Fieldbus connectors can be ordered from Endress+Hauser as an accessory (see Section 8
' A ccessories' ) .
The connection technology of FOUNDATION Fieldbus™ allows measuring devices to be
connected to the fieldbus via uniform mechanical connections such as T-boxes, junction boxes,
etc.
This connection technology using prefabricated distribution modules and plug-in connectors
offers substantial advantages over conventional wiring:
• Field devices can be removed, replaced or added at any time during normal operation.
Communication is not interrupted.
• Installation and maintenance are significantly easier.
• Existing cable infrastructures can be used and expanded instantly, e.g. when constructing new
star distributors using 4-channel or 8-channel distribution modules.
Fig. 8: Connectors for connecting to the FOUNDATION Fieldbus™
A
Fieldbus connector
– 1 Blue wire: FF– (terminal 2)
– 2 Brown wire: FF+ (terminal 1)
– 3 Gray wire: shielding
– 4 Green/yellow wire: ground
B
Field indicator
Connector technical data:
• Degree of protection IP 67 (NEMA 4x)
• Ambient temperature range: –40 to +105 °C (–40 to +221 °F)