Installation of optional air panel: P-AP56NAM

17 INSTALLATION OF OPTIONAL AIR PANEL: P-AP56NAM

17.1 APPLICABLE MODEL

This air panel is applicable to the following indoor unit model:
Air panel
P-AP56NAM
17.2 TRANSPORTATION AND HANDLING
1 Transport the air panel without unpacking as close to the
installation location.
2 Mount the air panel as soon as possible after unpacking.
3 When the air panel is placed on the floor after unpacking,
place it with the rear side downward (the surface to fit the
indoor unit body) on an insulation material, etc. However,
do not leave the air panel on the floor for long time. It may
cause air leakage due to scratch the seal packing.
17.3 BEFORE INSTALLATION
1 Check to ensure that the following accessories are packed with the air panel.
Name
Long Screw (M5 Cross Screw)
If any of these accessories are not packed in the packing, please contact your contractor.
17.4 INSTALLATION
!
C A U T I O N
Pay attention to perform the installation work at high-place using a
stepladder, etc.
?
N O T E
Do not move the louvre by hand.
If moved, the louvre mechanism will be damaged.
In addition, do not apply an excessive force to the air outlet part to
prevent the breakage.
1 The suspension height of the indoor unit should be referred
to "Installation & Maintenance Manual" of the indoor unit.
2 Do not touch the louvre during the installation work.
3 Remove the air inlet grille from the air panel.
34
PMML0363A rev.2 - 08/2016 - P5416559
Indoor unit model
RCIM-0.6FSN4 to 2.5FSN4
Quantity
Purpose
4
For fixing air panel
In addition, if the air panel is placed with the surface
downward, the louvre mechanism may be damaged due to
touch the louvre to the floor, etc.
4 Do not move the louvre by hand. If moved, the louvre
mechanism will be damaged.
While pushing both ends of knobs at the air inlet grille
toward the arrow direction, open the air inlet grille until the
angle of approximately 45° from the air panel surface. After
lifting the air inlet grille keeping it inclined, draw the air inlet
grille forward.
(Remove the filament tape (4 portions) fixing the air filter.)
Air inlet grille
Corner pocket
cover (4 portions)
?
N O T E
Although the air inlet grille can be opened until the angle of 90° from the
air panel surface, it can not be removed from the air panel.
Air panel
Knob