Test run
2 The total number of connected indoor units is indicated
on the LCD (Liquid crystal display). In the case of the twin
combination (a set of two (2) indoor units), the total number
of connected indoor units is indicated as "2 units", and in
the case of the triple combination (a set of three (3) indoor
units), the total number of connected indoor units is indicated
as "3 units".
Test Run Setting: 2 units
MODE
SPEED
LOUV.
T-RUN TIME 120MIN
SEL.
ADJ
3 If the number of connected indoor units displayed on LCD
is incorrect, the auto-address function is not performed
correctly due to incorrect wiring, the electric noise, etc. Turn
OFF the power supply, and correct the wiring after checking
the following points (do not repeat turning ON and OFF
within 10 seconds):
-
Failure To Turn ON Power Supply For Indoor Unit
-
Incorrect Wiring
-
Loose Connection between Indoor Units or of Remote
Control Switch
-
Incorrect Setting of Indoor Unit Address (The indoor unit
address is overlapped.)
4 Press " " (run/stop) to start the test run.
5 Press "
" and set each item.
Press " " (run/stop). As the air flow volume "HIGH" (default
setting) is indicated and the RUN indicator turns ON and
then the test run operation starts. 2-hour OFF timer will be
set automatically.
Test Run: 2 units
MODE
SPEED
LOUV.
T-RUN TIME 120MIN
SEL.
ADJ
40
PMML0363A rev.2 - 08/2016 - P5416559
COOL
MED
RUN
RTN.
COOL
HIGH
STOP
Press " " or " " and select "LOUV". Select "
by pressing " " or " ". Then the auto swing operation starts.
Check the operating sound of the louvres. If an abnormal sound
is generated from louvres, it may be caused by a deformation
of the air panel due to incorrect installation. In this case, install
the air panel again without a deformation. If an abnormal sound
is not generated, press " " or " " again to stop the auto swing
operation.
Test Run: 2 units
MODE
SPEED
LOUV.
T-RUN TIME 120MIN
SEL.
ADJ
The louvre indication will be changed as follows:
LCD indication
LCD Indication
Check to ensure that the motion sensor is operated correctly
as following procedures (in the case of the air panel with the
motion sensor).
Press and hold " " (menu) and "?" (help) simultaneously
for at least 3 seconds during the test run mode. The check
menu screen "A" is displayed.
"A"
Check Menu
Check 1
Check 2
Alarm History Display
Model Display
Function 5
SEL.
Select "Check 1" at the check menu and press "OK". (screen
"B" will be displayed.) (This screen is NOT displayed when
the number of indoor unit connected with the remote control
switch is 1(one). In this case, screen "C" will be displayed.)
"B"
Check 1
01-01
02-01
01-02
02-02
01-03
02-03
01-04
02-04
SEL.
" (auto swing)
COOL
HIGH
STOP
01
/
02
ENT.
RTN.
OK
03-01
04-01
03-02
04-02
03-03
04-03
03-04
04-04
RTN.
OK