Herunterladen Inhalt Inhalt Diese Seite drucken

Chauvin Arnoux DTR 8510 Bedienungsanleitung Seite 52

Der übersetzungsverhältnisse
Inhaltsverzeichnis

Werbung

Verfügbare Sprachen
  • DE

Verfügbare Sprachen

  • DEUTSCH, seite 82
The Set Clock configuration allows you to format the following:
Date Format: Allows the formatting of the date.
(MM/DD/YY, DD/MM/YY, YY/MM/DD).
Time Format: Allows the formatting of the time (12 or 24 hours).
Set Date and Time: Allows the setting of the date and time in the selected format.
Note: Time must be set in the 24-hour format. It will be displayed with AM/PM if the 12-hour format is chosen.
Example: To set the time to 2:50 PM, set the hour to 14 and the minutes to 50.
To maneuver between the Set Clock configuration settings, perform the following:
1.
Within the top level of Configure Instrument, press the  or  key until Set Clock appears on the display, then press ENTER
to configure the date.
2.
Use the  or  keys to view the choices. Press ENTER to make a selection. Once the format is selected, the display returns
to Date Format.
3.
Use the  or  keys to navigate to the other date and time options or press both  and  keys together to return to the
top level.
4.3.2. SETUP NAMEPLATE
Nameplate values are primary and secondary voltages (or ratios) associated with a given transformer. This information is avail-
able on the Nameplate of the transformer. The measured results will be compared with selected (edited) Nameplate values and
Deviation will be displayed and stored in % relative to these values.
The DTR
8510 allows the storage of 10 Nameplate voltages or ratios which can be individually selected for a given test.
®
NOTE:
„ The Nameplate list of up to 10 transformers can be written to and saved only using DataView
can be edited for use but cannot be saved from the front panel.
„ The keys on the front panel can select any one of the 10 transformer Nameplate values. Once the transformer values are
selected, they can be edited to a new value using the ,  and ENTER keys. When the new values are selected (even if they
are not edited to new values), it becomes the Present Nameplate and will be used for all subsequent VT/PT and CT measure-
ments. Deviation will be reported and stored using these values.
„ The Present Nameplate values will be retained in memory even if the instrument is turned OFF and turned ON. However, it
will not be saved in the list from which it was originally selected.
„ The user can select another Nameplate from the list in the future and may or may not edit the values. As soon as the new
Nameplate values are selected (and/or edited), it becomes the new Present Nameplate.
„ The Present Nameplate values are displayed in the Main Screen.
Figure 4-6
Figure 4-7
Figure 4-8
52
software. The values in the list
®

Werbung

Inhaltsverzeichnis
loading

Diese Anleitung auch für:

P01157702

Inhaltsverzeichnis