3. Specifications
Model
Noise level (50/60 Hz)
External static pressure
Indoor units
Total capacity
Model
Quantity
Operation
Standard type
temperature
Fresh air intake
type
Model
Noise level (50/60 Hz)
External static pressure
Indoor units
Total capacity
Model
Quantity
Operation
Standard type
temperature
Fresh air intake
type
4. Confirmation of parts attached
1 Conduit mounting plate (ø53)
Model
P200
P250 ~ P350
P400 ~ P650
5 Tapping screw M4
Model
P200
P250 ~ P350
P400 ~ P650
5. Space required around unit
[Fig. 5.0.1] (P.2)
<A> Top view
<C> When there is little space up to an obstruction
A Front
B No restrictions on wall height (left and right)
C Air outlet guide (Procured at the site)
E Wall height (H)
(mm)
L
L
1
2
450
450
(1) Basic space required
(2) When there is an obstruction above the unit
(3) When inlet air enters from right and left sides of unit
•
Wall heights "H" of the front and the back sides shall be within total height of
unit.
•
When wall height "H" exceeds total height of unit, add "h" dimension to L
L
of the Fig. 5.0.1.
2
"h" = wall height "H'" – total height of unit
6. Lifting method
[Fig. 6.0.1] (P.2)
Caution:
Be very careful to carry product.
- Do not have only one person to carry product if it weighs more than 20 kg.
- PP bands are used to pack some products. Do not use them as a mean for transportation because they are dangerous.
- Do not touch heat exchanger fins with your bare hands. Otherwise you may cut your hands.
- Tear plastic packaging bag and scrap it so that children cannot play with it. Otherwise plastic packaging bag may suffocate children to death.
- When carrying outdoor unit, be sure to support it at four points. Carrying with 3-point support may make outdoor unit unstable, resulting in it falling.
8
PU(H)Y-P200
PU(H)Y-P250
56 dB<A>
57 dB<A>
1 ~ 13
1 ~ 16
Cooling mode: – 5 °CDB ~ 43 °CDB (0 °CDB ~ 43 °CDB with outdoor unit at lower position)
Heating mode: – 20 °CWB ~ 15.5 °CWB
Cooling mode: 21 °CDB ~ 43 °CDB
Heating mode: – 12.5 °CWB ~ 20 °CWB
PUHY-P450
PUHY-P500
60/61 dB<A>
60/61 dB<A>
1 ~ 24
1 ~ 24
Cooling mode: – 5 °CDB ~ 43 °CDB (0 °CDB ~ 43 °CDB with outdoor unit at lower position)
Heating mode: – 20 °CWB ~ 15.5 °CWB
Cooling mode: 21 °CDB ~ 43 °CDB
Heating mode: – 12.5 °CWB ~ 20 °CWB
2 Conduit mounting plate (ø46)
–
–
1 pcs.
6 Connecting pipe (Flare)
2 pcs.
2 pcs.
2 pcs.
<B> Side view
D Must be open
F No restrictions on wall height
1
PU(H)Y-P300
59 dB<A>
0 Pa
50 ~130 %
20 ~ 250
1 ~ 19
PUHY-P550
61/62 dB<A>
0 Pa
50 ~130 %
20 ~ 250
1 ~ 24
3 Conduit mounting plate (ø33)
–
1 pc.
–
1 pc.
1 pc.
6 Connecting pipe (Flange)
1 pc.
–
1 pc.
–
1 pc.
(4) When unit is surrounded by walls
Note:
•
Wall heights "H" of the front and the back sides shall be within overall
height of unit.
•
If the panel height is exceeded, add the "h" dimension of the Fig. 5.0.1 to
L
and L
.
1
2
(mm)
L
L
1
2
450
450
Example: When the "h" dimension is 100 mm,
the L
dimension becomes 450 + 100 = 550 mm.
1
(5) Collective installation and continuous installation
•
Space required for collective installation and continuous installation:
When installing several units, provide the space between each block consider-
ing passage for air and people.
and
•
Open in two directions.
•
In case of wall height "H" exceeds total height of unit, add "h" dimension (h =
wall height "H'" – total height of unit) to * marked dimension.
•
If there is a wall at both the front and the rear of the unit, install up to four units
(Every 3 units in the case of P450 ~ P650.) consecutively in the side direction
and provide a space of 1000 mm or more as inlet space/passage space for
each four units (Every 3 units in the case of P450 ~ P650.) .
PU(H)Y-P350
PUHY-P400
60 dB<A>
1 ~ 20
PUHY-P600
PUHY-P650
61/62 dB<A>
62/62.5 dB<A>
1 ~ 32
4 Conduit mounting plate (ø27)
1 pc.
1 pc.
–
–
7 Packing (inside ø23, outsideø35)
–
–
1 pc.
1 pc.
61 dB<A>
1 ~ 22
1 ~ 32