CP-Parameter
The signals A(+) and A(-) must be changed for units with SIN/COS encoder. Should this
involve too much effort then you can achieve a rotation reversal of encoder 1 by means
of this parameter.
CP.21 Meaning
0
Tracks not exchanged
1
Track exchanged
2...3 Reserved for initiator input
CP.28 Torque reference source
With CP.28 the required setpoint source for torque control can be adjusted.
CP.28 Meaning
0
AN1+ / AN1-
1
AN2+ / AN2-
2
Digital absolute
3...5 Only application mode
CP.33 Relay output 1 / function
CP.34 Relay output 2 / function
CP.33/34 determine the function of the two relay outputs (X2A.24-26, X2A.27-29).
Value Function
0
No function (generally off)
1
Generally on
2
Run signal; also by DC-braking
3
Ready signal (no error)
4
Fault relay
5
Fault relay (without auto-reset)
6
Warning or error message after abnormal stopping
7
Overload pre-warning
8
Overtemperature alert signal power stage
9
Ex. overtemperature pre-warning motor
11
Overtemperature pre-warning OHI
20
Actual value = set value (CP.3 = Fcon, rcon, not at noP, LS, error, SSF)
21
Accelerate (CP.3=FAcc, rAcc, LAS)
22
Decelerate (CP.3 = FdEc, rdEc, LdS)
23
Real direction of rotation = set direction of rotation
24
Utilization > switching level
25
Active current > switching level
27
Real value (CP.1) > switching level
28
Setpoint (CP.2) > switching level
31
Absolute setpoint on AN1 > switching level
32
Absolute setpoint on AN2 > switching level
34
Setpoint at AN1 > switching level
35
Setpoint at AN2 > switching level
40
Hardware current limit activated
41
Modulation on-signal
47
Ramp output value>switching level
48
Apparent current (CP.4) > switching level
49
Forward running (not at nOP, LS, abnormal stopping or error)
50
Reverse running (not at nOP, LS, abnormal stopping or error)
51
Warning E.OL2
52
Current regulator limit reached
53
Speed regulator limit reached
Setting Range
0%...±100% = 0...±CP.29
0%...±100% = 0...±CP.29
0...±CP.29
1)
1)
1)
1)
1)
1)
1)
1)
1)
1)
GB - 37

Quicklinks ausblenden:

Werbung

Kapitel

Inhaltsverzeichnis
loading

Diese Anleitung auch für:

Combivert f5

Inhaltsverzeichnis