CP-Parameter
CP.35 Reaction to limit switch
This parameter determines the reaction of the drive to terminal X2A.14 (F) and/or X2A.15
(R), which are programmed as limit switches. The reaction of the drive is shown in the
table below.
CP.35 Display Reaction
0
E.PRx Immediate disabling of modulation
1
A.PRx
2
A.PRx Quick stopping / holding torque at speed 0
3
A.PRx Immediate disabling of modulation
4
A.PRx
5
A.PRx Quick stopping / holding torque at speed 0
6
none
CP.36 Reaction to external fault
With the external error monitoring external units can take direct influence on the drive.
This parameter determines the response of the drive to a signal at terminal X2A.12 (I3)
according to following table.
CP.36 Display Reaction
0
E.PRx Immediate disabling of modulation
1
A.PRx
2
A.PRx Quick stopping / holding torque at speed 0
3
A.PRx Immediate disabling of modulation
4
A.PRx
5
A.PRx Quick stopping / holding torque at speed 0
6
none
GB - 34
Quick stopping / disabling of modulation after
reaching speed 0
Quick stopping / disabling of modulation after
reaching speed 0
No effect to the drive, fault is ignored !
Quick stopping / disabling of modulation after
reaching speed 0
Quick stopping / disabling of modulation after
reaching speed 0
No effect to the drive, fault is ignored !
Restart
Remove fault,
reset
Autoreset, if no fault
is present
inapplicable
Restart
Remove fault,
reset
Autoreset, if no fault
is present
inapplicable