If several extension handles with HV STK... plug-in coupling are used, the combination of the
PHE III... voltage detector (with attached test prods, if any) and the insulating stick (with all
extensions) must not exceed a total length of 7000 mm.
!
Do not contact the section above the handguard
The insulating section (insulating clearance) of the voltage detector must not contact live parts of the installation.
2
The entire test prod
ring.
The "voltage present" indication must appear if the line-to-earth voltage of the part to be tested is more than
45% of the nominal voltage. The "voltage present" indication must not appear if the line-to-earth voltage of the
part to be tested is equal to or less than 10% of the nominal voltage. Observe the impact of interference fields.
Note:
The values mentioned above only refer to voltage detectors for use in three-phase systems. The response values of
special versions (observe note on the rating plate!) for other systems such as single-ended or centre-earthed
monophase systems are rated according to the relevant system configuration.

5.1 Rating plate:

The technical data (nominal voltage, nominal frequency) and instructions on the rating plate must be observed
(see Fig. 5.1).
5.2 Nominal voltage / nominal voltage range
The PHE III... voltage detector series includes
both devices with only one nominal voltage and
devices with a nominal voltage range and
switchable nominal voltage range.
The response behaviour of PHE III... voltage
detectors depends on the nominal voltage U
or nominal voltage range specified on the
rating plate. The insulation strength and
protection against bridging of the voltage
detectors are rated for the max. equipment
voltage U
. Voltage detectors may only be
r
used for the following max. equipment
according to their nominal voltage
voltages U
r
U
(see Table 5.2).
n
U
/ kV
3
n
U
/ kV
3,6
r
* only for systems with efficiently earthed neutral point
of the voltage detector may contact live and earthed parts of the installation up to the red
6
10
15
7,2
12
17,5
!
5
n
Fig. 5.1
20
30
45
24
36
52
Page 11
60
110
132*
72,5
123
145*
1598_0314_ Mat No. 69682
150*
170*