(7) Set step (6) value as a sensor correction value.
(8) Enter an electromotive force or resistance value equivalent to 750
(9) Read the PV, and confirm that 700
Auxiliary function setting mode 2
5.4
To enter auxiliary function setting mode 2, press and hold the UP, DOWN and MODE keys (in that order)
together for approx. 3 seconds in PV/SV display mode.
Character factory default
is indicated.
Setting item, function, setting range
Input type
• The input type can be selected from thermocouple (10 types), RTD (2
types), DC current (2 types) and DC voltage (4 types), and the unit
can be selected as well.
• When changing the input from DC voltage to other inputs, remove the
sensor connected to this instrument first, then change the input. If the
input is changed with the sensor connected, the input circuit may break.
(Table 5.4-1)
Character
Input range
K -200 to 1370
K -200.0 to 400.0
J -200 to 1000
R 0 to 1760
S 0 to 1760
B 0 to 1820
E -200 to 800
T -200.0 to 400.0
N -200 to 1300
PL-
0 to 1390
C(W/Re5-26) 0 to
2315
Pt100 -200.0 to
850.0
JPt100 -200.0 to
500.0
Pt100 -200 to 850
JPt100 -200 to 500
4 to 20 mA DC -2000 to 10000
(Externally mounted 50
0 to 20 mA DC -2000 to 10000
(Externally mounted 50
0 to 1 V DC -2000 to 10000
0 to 5 V DC -2000 to 10000
1 to 5 V DC -2000 to 10000
0 to 10 V DC -2000 to 10000
4 to 20 mA DC -2000 to 10000 (Built-in 50
resistor)
0 to 20 mA DC -2000 to 10000 (Built-in 50
resistor)
13
using an mV generator or dial resistor.
Character
Input range
K -320 to 2500
K -200.0 to 750.0
J -320 to 1800
R 0 to 3200
S 0 to 3200
B 0 to 3300
E -320 to 1500
T -200.0 to 750.0
N -320 to 2300
PL-
0 to 2500
C(W/Re5-26) 0 to 4200
Pt100 -200.0 to 1000.0
JPt100 -200.0 to 900.0
Pt100 -300 to 1500
JPt100 -300 to 900
shunt resistor)
shunt resistor)
/
shunt
shunt