Inrush current:
Measuring range
5.0 A - 400 A
Integration time: 100 ms
Threshold value of the trigger current: 5 A
7.2 DC current range (BENNING CM P2)
Measuring range
40.00 A
40.1 A - 400 A
8.
Measuring with the BENNING CM P1/ P2

8.1 Preparing the measurement

Operate and store the BENNING CM P1/ P2 at the specified storage and operating tempera-
tures only! Do not permanently expose the device to sunlight.
-
Strong sources of interference in the vicinity of the BENNING CM P1/ P2 might involve
unstable readings and measuring errors.

8.2 Current measurement

Do not exceed the maximum permitted voltage with respect to earth potential!
Electrical danger!
For direct current (DC) measurements (BENNING CM P2), observe correct
polarity! The arrow on the measuring clamp indicates the technical current
direction. + → –
-
After switching it on, the BENNING CM P1/P2 is automatically in function A. Otherwise,
press the A key 8 .
-
For the BENNING CM P2, press the A key 8 to select the desired function A
the A
function, press the null balance key ∆/LPF 6 to switch the BENNING CM P2 to the
initial mode.
-
Operate opening lever  , clamp  single wire live conductor centrally by means of the
BENNING CM P1/ P2 current probe.
-
Read off the digital display unit J .
See figure 2:
Current measurement
8.3 Voltage indicator (NCV)
The voltage indicator function is not intended for testing the absence of volt-
age. Even without an indication or acoustic signal, a dangerous contact volt-
age might be applied. Electrical danger!
The voltage indicator function is intended for non-contact detection of an alternating field.
The detector 2 is located on the measuring clamp within the  NCV  marking. Switch the
BENNING CM P1/P2 on and select the voltage indicator function by pressing the NCV key 7 .
The digital display J shows the „
acoustic signal will be emitted and the intensity of the alternating field will be indicated on the
digital display J by a maximum of 4 bars "- - - -". An indication is made in earthed AC current
networks only!
03/ 2018
Resolution
Measurement accuracy (50 Hz - 60 Hz)
0.1 A
Resolution
0.01 A
0.1 A
" and "EF" symbols. If a phase voltage is localized, an
BENNING CM P1/ P2
± (3.5 % of reading + 8 digits)
Measurement accuracy
± (2.0 % of reading + 5 digits)
± (2.0 % of reading + 5 digits)
Overload protection
420 A eff.
Overload protection
420 A eff.
420 A eff.
or A. In
17