Herunterladen Inhalt Inhalt Diese Seite drucken

Steca StecaGrid 8000 3ph Installations- Und Bedienungsanleitung Seite 44

Inhaltsverzeichnis

Werbung

Verfügbare Sprachen

Verfügbare Sprachen

4.6.2 Settings on the inverter interface card
The address and termination of the inverter are set on the interface card. The in-
terface card must be removed to make these settings.
2
1
5
1 AC socket
2 DC circuit breaker
3 Negative inputs
4 Positive inputs
5 Interface card
Removing the interface card
Danger
Risk of death by electrocution!
All work must be performed with the inverter removed from all power sources.
X
Always perform the following steps in the sequence described.
1. Set the DC switch to 0.
2. Remove the AC cable by releasing the locking device on the AC plug.
3. Make sure that the DC switch and AC cable cannot be unintentionally
switched on / plugged in.
4. Remove the data cable. Grasp the cable by the plug to open the push-pull
locking mechanism.
5. Remove the four Phillips screws holding the interface card.
6. Pull the interface card out of the slot. Grasp the card by the protruding black
collars of the RJ45 sockets. Place the seal to one side.
Setting the inverter address
1. Use a screwdriver to set the rotary switches to the desired address.
2. Write down the address to make error-finding easier in the case of address
conflicts.
Switching on the termination
Slide the DIP switch towards the RS485 connectors. Use a pointed implement if
X
necessary, e.g. a ballpoint pen.
Installing the interface card and making connections
1. Mount the seal on the interface card.
2. Insert the interface card into the side rails and slide it into place until it latch-
es in place.
3. Fasten the interface card with the four Phillips screws.
4. Plug in the data cable.
5. Plug in the AC cable.
44
3
3
4
4
EN
737.096 | 11.37

Werbung

Inhaltsverzeichnis
loading

Diese Anleitung auch für:

Stecagrid 10000 3ph

Inhaltsverzeichnis