Measurements are taken between a grounded point and the touchable, conductive part
which is not connected with the ground conductor.
The contact current must not exceed 0.5 mA *).
1 Measuring instrument
2 Inverter
6.2 Touchable, conductive part not connected to the
ground conductor
8 Insulated assembly of the object being tested
9 Measurement lead
Ri 1–2 k
*) These requirements relate to DIN VDE 0701-0702 and ÖVE/ÖNORM E8701-1. In addi-
tion, individual national requirements and standards must also be observed.
156
PE
L1
R i
mA
1-2kΩ
1
9
9
PE
L1
6.2
N
N
2
8
Touchable, conductive parts not connected to the
ground conductor