Fronius 10.0-1 Serviceanleitung Seite 105

Primo 208-240
Inhaltsverzeichnis

Werbung

Verfügbare Sprachen

Verfügbare Sprachen

Code
Description
481
Recerbo has old software
version
482
Inverter switched off during
commissioning
483
Set DC2 fixed voltage out-
side of the permitted MPP
range
484–485
Error during data transfer
Service Class 5–6
Class 5–6 status codes generally do not impair grid power feed operation, but can result
in limitations to it. They will be displayed until the status code is acknowledged by pressing
a key (the inverter, however, continues working normally in the background).
Code
Description
502
An insulation fault was de-
tected between DC+/DC-
and the ground
509
No grid power feed opera-
tion over 24 hours
515
EEPROM communication
failed
516
Communication error in
power module
517
Power module derating
caused by excessive tem-
perature
Behavior
1. Old Recerbo software
2. Old software
3. Incompatible hardware com-
bination
1. Startup process not suc-
cessful
1. Incorrectly set fixed voltage
1. Communication problem
caused by temporary environ-
mental faults (grid, EMC, etc.)
2. Ribbon cable between filter
PC board and power module
faulty
3. Faulty AC guard on filter PC
board
4. Faulty AC guard on power
module
Behavior
1. Insulation fault in PV gener-
ator
1. Modules covered by snow or
very dirty
2. For grid power feed opera-
tion of modules
1. Occurs once
2. Filter calibration value incor-
rect
1. Occurs once
2. Power module faulty
1. Ventilation opening blocked
2. Ambient temperature too
high
3. Disconnected fan cable
4. Fan faulty
5. Bad contact: power module
<--> heat sink
6. Filter PC board faulty
7. Recerbo faulty
8. Measurement error on pow-
er module
Remedy
1. Software update
2. Reload setup
3. Check hardware compo-
nents
1. Restart inverter
1. Check settings
1. Automatically corrected
2. Replace ribbon cable
3. Replace filter PC board
4. Replace AC PC board
Remedy
1. Check cable and PV gener-
ator
1. Clean modules or remove
snow
2. Check other service codes
1. Restart inverter
2. Replace AC PC board and
then, if necessary, DC PC
board
1. Restart inverter
2. Replace power module
1. Clean ventilation openings
2. Change setup location
3. Connect fan cable
4. Replace fans
5. Check phase change paste
6. Replace filter PC board
7. Recerbo faulty
8. Replace power module
105