Code
Description
301
Current peak found on grid
302
Current peak found on PV
generator
303
Heat sink temperature too
high
306
POWER LOW
307
DC LOW
308
The intermediate circuit
voltage exceeds max. per-
missible limit
100
Behavior
1. Voltage drop in public grid
2. Grid impedance outside of
permissible values
3. Bad contact: wall bracket <-
-> inverter
4. Measurement error on filter
PC board
5. Incorrect capacity on device
1. Bad contact: wall bracket <-
-> inverter
2. Voltage drop in public grid
3. Measurement error on pow-
er module
1. Ventilation opening blocked
2. Ambient temperature too
high
3. Internal or external fans not
connected
4. Internal or external fans
faulty
5. Bad contact: power module
<--> heat sink
6. Measurement error on pow-
er module
7. Ventilator power on Recerbo
faulty
1. DC power too low for infeed
2. Measurement error on pow-
er module
1. Open the main DC switch.
2. PV generator not connected
3. DC voltage too low for infeed
4. Reverse voltage of PV gen-
erator
5. DC operating mode: fixed
voltage + incorrect voltage
6. Measurement error on pow-
er module
1. Voltage drop in alternating
current grid
2. Bad contact: wall bracket <-
-> inverter
3. Measurement error on pow-
er module
Remedy
1. Automatic correction
2. Contact energy provider
3. Check fixing screws in DAT-
COM area
4. Replace filter PC board
5. Replace AC power module
1. Check fixing screws in DAT-
COM area
2. Automatic correction
3. Replace AC PC board Oth-
erwise replace DC PC board
1. Clean openings
2. Change setup location
3. Connect fan cable
4. Replace fans
5. Check phase change paste
6. Replace AC PC board
7. Replace Recerbo
1. Wait for more radiation in-
tensity or check solar modules
2. Replace DC PC board. Oth-
erwise replace AC PC board
1. Close the main DC switch.
2. Connect PV generator
3. Wait for more radiation in-
tensity or check solar modules
4. Reverse polarity of PV gen-
erator
5. Check MPP settings/voltag-
es
6. Replace DC PC board. Oth-
erwise replace AC PC board
1. Automatic correction
2. Check fixing screws in DAT-
COM area
3. Replace AC PC board