uk │ 7. Start-up
7.4.1 Supply air volumetric flow setting
1. Connect the voltmeter (measurement
range U
1...10 V) to connector pins
DC
1 and 3 (GND).
2. Select the corresponding ventilation level
1, 2 or 3 on the room air control (operator
unit).
3. Deactivate the CO2 sensor
(jumper 10 = open).
4. You can now set the defined voltage for
the required supply air volumetric flow for
the selected ventilation level (1, 2 or 3)
with one of the blue potentiometer
adjusters S1, S2 or S3.
5. You will find the defined voltage value for
the required volumetric flow in the table in
Chapter 7.3 (predefined voltage = f (volu-
metric flow).
Blue adjuster S1 for the predefined
voltage of ventilation level 1
Blue adjuster S2 for the predefined
voltage of ventilation level 2
Blue adjuster S3 for the predefined
voltage of ventilation level 3
7.4.2 Exhaust air volumetric flow setting
1. Connect the voltmeter (measurement
range U
1...10 V) to connector pins 5
DC
and 3 (GND).
2. Proceed exactly as described for supply air
volumetric flow setting and adjust the
defined voltage for the required exhaust air
volumetric flow with one of the red poten-
tiometer adjusters S1, S2 or S3.
Red adjuster S1 for the predefined voltage
of ventilation level 1
Red adjuster S2 for the predefined voltage
of ventilation level 2
Red adjuster S3 for the predefined voltage
of ventilation level 3
62

8. Accessories

Accessory / Product type
10x RBG 170 air filter,
filter class G4
RBG-ES 170 push-in frame
for G4 air filter
1x RBF 170 pollen filter,
filter class F7
1x RBF-AKF 170 active carbon
air filter, filter class F7
NTC 15 temperature sensor
with grommet
RB-ZF4
room air control
RB-D1-ZF4
digital control
RFS
humidity control
SKD
CO
sensor
2
VOC sensor:
EAQ 10/2 air quality sensor
Combi wall support, right-hand
version, suitable for RB 170 R,
RB 170 CR and RB 170 CBR
AKW-R-125
AKW-R-160 in conjunction with
ISO-Form Ø 125
Combi wall support, left-hand
version, suitable for RB 170 L,
RB 170 CL and RB 170 CBL:
AKW-L-125
AKW-L-160 in conjunction with
ISO-Form Ø 125
NPU-125
plug connector with lip seal
BU 125-90
pipe elbow
Article no.
0043.0270
0043.0269
0043.0271
0043.0272
0043.0833
0043.0570
0043.0828
0043.0716
0043.0576
0043.0834
0044.0223
0044.0199
0044.0222
0044.0198
0045.0036
0045.0104
Inhaltsverzeichnis
loading

Diese Anleitung auch für:

Rb 170 rRb 170 clRb 170 cr

Inhaltsverzeichnis