Konfiguration Schnittstellen / GLT
BACnet MS/TP Schnittstelle
Binary Value Objects
Property
Object_Identifier
Object_Name
Object_Type
Present_Value
Status_Flags
Event_State
Out_Of_Service
Inactive_Text
Active_Text
R: Read Property, W: Write Property, COVU: Unsolicited Change of Value Notification
Instance
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
PICS_X-AIRCONTROL_v1.0.doc
60
Remark / Value
binary-value, instance 1 ... 20
BINARY_VALUE (5)
INACTIVE (0, Initial) / ACTIVE (1)
IN_ALARM:
FAULT:
OVERRIDDEN:
OUT_OF_SERVICE:
NORMAL (0)
FALSE (0)
Object_Name
"StartPCM"
"Fire"
"Window"
"ExtraTime"
"ActExtraTime"
"ActWindow"
"FAlarm"
"Alarm1"
"Alarm2"
"Release"
"Status_PowerSupply"
"Status_EMFSLIO"
"Status_Fan"
"Status_Sensor"
"Status_Filter"
"Status_FlowControl"
"Status_Damper"
"ActFire"
"FanForce"
"ActFanForce"
Einzelraumregelung FSL‑CONTROL II
0
0
0
0
Inactive_Text
Active_Text
"Off"
"On"
"Normal"
"Fire"
"Close"
"Open"
"Inactive"
"Active"
"Inactive"
"Active"
"Close"
"Open"
"Normal"
"Frostalarm"
"Normal"
"Alarm1"
"Normal"
"Alarm2"
"Off"
"On"
"Normal"
"LowPower"
"Normal"
"ComFail"
"Normal"
"FanBlocked"
"Normal"
"SensorFail"
"Normal"
"FilterAlarm"
"Normal"
"FlowAlarm"
"Normal"
"CalibrationFail"
"Normal"
"Fire"
"Inactive"
"Active"
"Inactive"
"Active"
- 5 -
RW
R
R
R
R
R
R
R
R
Present_Value
RW
RW
RW
RW
R
R
R
COVU
R
COVU
R
COVU
R
R
COVU
R
COVU
R
COVU
R
COVU
R
COVU
R
COVU
R
COVU
R
RW
R